Specific embodiment
If normal grid voltage phase voltage peak value is VT, fall phase voltage peak value as n × VT(0≤n≤1), with VTAs base
Quasi- value carries out perunit, then, can according to unsymmetrical short-circuits modes such as network voltage single-phase earthing, two phase ground and two-phase phase faults
It respectively obtains Static Synchronous generator output voltage under network voltage asymmetry short circuit fault and expresses formula.
Single-phase grounding fault:
According to symmetrical component method, when short trouble occurs, if grid entry point voltage-phase does not change, list can obtain
Static Synchronous generator output positive sequence, negative phase-sequence, zero-sequence component amplitude are under phase ground short circuit failure:
This makes it possible to obtain three-phase voltage expression formula such as formulas 1 during singlephase earth fault) shown in:
In formula:Vp--- network voltage positive-sequence component;Vn--- network voltage negative sequence component;V0--- network voltage zero sequence
Component;vabc--- three-phase power grid voltage;N --- grid voltage sags amplitude.
Two relative ground circuit failures:
According to symmetrical component method, when short trouble occurs, if grid entry point voltage-phase does not change, two are can obtain
Static Synchronous generator output positive sequence, negative phase-sequence, zero-sequence component amplitude are under relative ground circuit failure:
This makes it possible to obtain three-phase voltage expression formula such as formulas 2 during two relative ground circuits) shown in:
In formula:Vp--- network voltage positive-sequence component;Vn--- network voltage negative sequence component;V0--- network voltage zero sequence
Component;vabc--- three-phase power grid voltage;N --- grid voltage sags amplitude.
Two-phase phase fault:
According to symmetrical component method, when short trouble occurs, if grid entry point voltage-phase does not change, two are can obtain
Static Synchronous generator output positive sequence, negative phase-sequence, zero-sequence component amplitude are under phase phase fault:
This makes it possible to obtain three-phase voltage expression formula such as formulas 3 during two-phase phase fault) shown in:
In formula:Vp--- network voltage positive-sequence component;Vn--- network voltage negative sequence component;V0--- network voltage zero sequence
Component;vabc--- three-phase power grid voltage;N --- grid voltage sags amplitude.
Accordingly, for the present invention under asymmetry short circuit fault, negative phase-sequence dynamic reactive support and control strategy is as follows:
Pass through positive-negative sequence separation control strategy realization positive sequence, the decoupling control of negative sequence component;
By formula 1), formula 2), formula 3), network voltage positive sequence, negative sequence component size after being detached according to positive-negative sequence, in real time calculate
Degree of unbalancedness;
According to degree of unbalancedness, by formula 4), by closed-loop control+instruction current Feed-forward Control Strategy, negative phase-sequence is exported in real time
Dynamic reactive electric current realizes the support to falling phase voltage.IeFor rated current.
The present invention will be further described in detail below in conjunction with the accompanying drawings.
H bridges cascade chain type Static Synchronous generator negative phase-sequence dynamic reactive support and control plan under power grid asymmetry short circuit fault
Slightly control structure block diagram is as shown in Fig. 2, whole system is detached by positive-negative sequence and phase lock control, negative-sequence current generate, negative phase-sequence refers to
Enable the compositions such as current limit and instruction feedforward, residual voltage control, submodule Pressure and Control.
(1) positive-negative sequence separation Decoupling network and phaselocked loop
When uneven or asymmetry short circuit fault occurs in network voltage, voltage is simultaneously comprising positive sequence, negative phase-sequence, zero sequence point
Amount, thus detaches positive and negative sequence component firstly the need of by Decoupling network shown in Fig. 3, locks positive sequence base on this basis
Wave component phase.
(2) power closed-loop control
Power closed-loop control is realized by receiving host computer or remote control end power instruction to Static Synchronous generated power work(
The accurate control of rate, reactive power.It is real in a manner that power feedforward is combined with closed-loop control to accelerate system response time
Existing, the output of power ring adjuster is watt current, referenced reactive current.According to instantaneous power theory, active power, reactive power
Value of feedback is respectively:
In formula:Pf--- instantaneous active is fed back;Qf--- instantaneous reactive is fed back;Vp--- network voltage positive-sequence component;
Ipd--- positive sequence watt current;Ipq--- positive sequence active component.
Active power, reactive power closed-loop control block diagram are as shown in Figure 4, Figure 5.
(3) negative current instructions generation and current limit
First, three-phase power grid voltage is detected in real time, and detaching Decoupling network according to positive-negative sequence respectively obtains negative phase-sequence, positive sequence voltage
Component, by formula 4) calculate negative phase-sequence dynamic reactive current-order;Secondly, positive-negative sequence separated network is to three-phase grid as shown in Figure 3
Electric current carries out positive-negative sequence separation, realizes positive sequence watt current, positive sequence active component, negative phase-sequence watt current, negative phase-sequence reactive current
Decoupling control;Finally, it under power grid asymmetry short circuit fault, to ensure negative-sequence current output, realizes and is moved to falling phase voltage
State supports, and forward-order current need to be instructed and carry out amplitude limit, specific strategy is as follows:
Positive sequence current values are calculated according to the active and reactive instruction current of positive sequence, such as formula 5) shown in;
Negative sequence current value is calculated according to the active and reactive instruction current of negative phase-sequence, such as formula 6) shown in;
Amplitude limit principle is that the sum of positive sequence, negative phase-sequence instruction current are no more than the Static Synchronous rated current of generator, and in electricity
Under net asymmetry short circuit fault, should be preferential using negative-sequence current output, obtain forward-order current amplitude limit value such as formula 7 accordingly) shown in.
In formula:--- forward-order current instructs;--- positive sequence watt current instructs;--- positive sequence is idle
Current-order;--- negative current instructions;--- negative phase-sequence watt current instructs;--- negative phase-sequence reactive current refers to
It enables;Ie--- rated current.
(4) residual voltage controls
The guarantee of residual voltage control program is alternate to press, and under power grid asymmetry short circuit fault, still ensures that H bridge cascade chains
The equilibrium of DC voltage, control structure block diagram are as shown in Figure 6 on formula structure three chains of static synchronous generator.First, it calculates
Three respective DC voltage average values of chain, after passing it through three-phase to two phase inversions, zero is can be calculated by pi regulator
Sequence voltage phase and amplitude information, the value are residual voltage;Secondly, active and reactive electricity is exported according to Static Synchronous generator
Stream and the output of residual voltage controller determine residual voltage phase information;0 that finally residual voltage is converted as dq0 → abc
Axis component, be added to each submodule after 2r → 3s transformation.
Can be realized under power grid asymmetry short circuit fault by above-mentioned control strategy only imbalance is fallen the voltage of phase into
Mobile state reactive power support, overcompensation overpressure problems caused by effectively preventing original control strategy.Simultaneously as employ instruction
Current limit strategy, it is ensured that as degree of asymmetry increases, to export negative phase-sequence reactive current to greatest extent, realize maximum
Negative-sequence current support and control.
Specific embodiment is presented above, but the present invention is not limited to described embodiment.The base of the present invention
This thinking is above-mentioned basic scheme, and for those of ordinary skill in the art, various changes are designed in introduction according to the present invention
The model of shape, formula, parameter do not need to spend creative work.It is right without departing from the principles and spirit of the present invention
The change, modification, replacement and modification that embodiment carries out are still fallen in protection scope of the present invention.